Its daughter company, EDP Distribuição Energia S.A., is the largest utility in Portugal with some 400 distribution substations controlled by two HV Dispatch Centers. Six Control Centers assure the operation of the MV network, with more than 4.000 feeders and 70.000 km of lines and cables. The company constantly invests in the further improvement of the already high service and supply quality to its over 5.9 million customers. To satisfy their growing demand for power, it adopts latest technologies in its infrastructures and embarked in utilizing IEC 61850, the global standard for communication in substations, soon after it was published.
IEC 61850-compliant substation automation systems shall be implemented in six HV/MV substations. The stations Cacém, Aeroporto, Glória, Serpa, Venda do Pinheiro and Parede are of high importance for the grid as they supply power to urban regions as well as the Lisbon airport. The stations shall be monitored and controlled both locally as well as remotely and maintenance access be provided for setting, diagnosis and correction purposes. The systems shall utilize the standard’s features, e.g. horizontal communication via GOOSE messages for distributed functions. The system architecture and network topology shall be standardized throughout the grid.
Our solution
The SAS 630 substation automation solution with verified IEC 61850-implementation provides local control via Station HMI as well as remote command and data access from the NCC via integrated gateway. The standardized high-quality operator interfaces, functions and system layouts help optimize operation and maintenance. Safe remote maintenance access to all IEDs on the LAN can be established via modem or Ethernet.
All control and protection IEDs are IEC 61850-compliant. They exchange some 150 binary signals via GOOSE messages to perform vendor-specific distributed functions. Amongst others these include interlocking, circuit breaker failure protection (CBFP), decentralized voltage and frequency load shedding, automatic voltage restoration after load shedding, automatic protection setting group adjustment according to neutral as well as varimetric and hourly control of capacitor banks.