ETL600 R4 - Power line carrier system

ETL600 R4 - Power line carrier system is an advanced PLC solution for secure communication of speech signals, data, and protection commands in critical setups.
Product image for: ETL600 R4 - Power line carrier system

The secure communication solution for critical infrastructures.

Universal Power Line Carrier System ETL600 R4 (ETL600) is an advanced PLC solution for the transmission of speech signals, data and protection commands over high-voltage transmission lines. With its universal hardware and software architecture, ETL600 simplifies the decision between traditional analog and advanced digital PLC equipment.

Using the same hardware components, the operating modes Digital or Analog can be selected by the user on site with just a few mouse clicks. In addition to user-friendliness combined with application flexibility and unprecedented data transmission speed, ETL600 also guarantees unconditional compatibility with legacy environment and integrates well into modern digital telecommunication infrastructures.

Get to know more

Operating mode 2-wire frequency duplex
Modulation Single side band with suppressed carrier (SSB)
Multi-Carrier Modulation with Trellis Coding and Forward Error Correction
Single step frequency conversion with Direct Digital Synthesis (DDS)
Nominal bandwidth 2, 4, 8, 12, 16, 20, 24, 28, 32 kHz (each direction)
Edge frequencies at multiples of 500 Hz
Carrier frequency range 24 to 1000 kHz for nominal bandwidth ≥ 4 kHz
24 to 500 kHz for 2 kHz nominal bandwidth
Standards compliance IEC 60495, IEC 60834-1, IEC 60950-1, IEC 61000-6-2, 
IEC 61000-6-4 (EN 55022 / CISPR22, Class A)
Nominal transmit output power (PEP) ETL600-050: 50 W / +47 dBm,
ETL600-100: 100 W / +50 dBm
(may be decreased via user interface program HMI in steps of 1 dB)
Nominal output impedance 75 Ohm unbalanced
150 Ohm balanced as option
Return loss in the transmitter band > 10 dB according to IEC 60495
Tapping loss < 1.5 dB according to IEC 60495
Receiver sensitivity -30 dBm pilot level at the RF input
Receiver selectivity > 65 dB / > 75 dB at 300 Hz / 4 kHz from the band edges 
(for nominal bandwidth > 2 kHz)
Image rejection > 75 dB
AGC (Automatic Gain Control) range > 40 dB
Power supply -48 VDC +20/-15 % (other on request)
Power consumption 
ETL600-050
ETL600-100
Normal operation @ 75 Ohm
135 to 155 W (1 to 3 APLC ch.)
210 to 230 W (1 to 3 APLC ch.)
Dual tone modulation PEP @ 75 Ohm
175 to 195 W (1 to 3 APLC ch.)
280 to 300 W (1 to 3 APLC ch.)
Alarm relay outputs Free changeover contacts
- System alarm / cabinet alarm
- Hardware alarm 
- Link alarm
- Interface alarm
- Warning
Event recording 2600 time-stamped alarm and manipulation events
2600 time-stamped command events
stored in nonvolatile memory
Clock synchronizing input for IRIG-B available